Model No. - DRA-40 Series
Max Output Wattage (W) - 40 Watts
Output Voltage (VDC) – 13.8, 27.6 Volts
Model No. |
DRC-40A |
DRC-40B | |||
Output: |
Output Number |
CH1 |
CH2 | CH1 | CH2 |
DC Voltage |
13.8V |
13.8V | 27.6V |
27.6V |
|
Rated Current |
1.9AA |
1A | 0.95A |
0.5A |
|
Current Range |
0 ~ 2.9A |
-------- | 0 ~ 1.45A |
---------- |
|
Rated Power |
40.02W |
40.02W | |||
Ripple & Noise (max.) Note 2 |
120mVp-p |
--------- | 200mVp-p |
--------- |
|
Voltage ADJ. Range |
CH1: 12 ~ 15V |
CH1:24 ~ 30V | |||
Voltage Tolerance Note 3 |
±1.0% |
--------- | ±1.0% |
--------- |
|
Line Regulation Note 4 |
±0.5% |
--------- | ±0.5% |
--------- |
|
Load Regulation Note 5 |
±0.5% |
--------- | ±0.5% |
---------- |
|
Setup, Rise Time |
400ms, 50ms/230VAC 800ms, 50ms/115VAC at full load | ||||
Hold up Time |
50ms/230VAC 10ms/115VAC at full load |
||||
Input: |
Voltage Range |
90~264VAC 127~370VDC [DC input operation possible by connecting AC/L(+), AC/N(-)] |
|||
Frequency Range |
47~63Hz |
||||
Efficiency (Typ.) |
86% |
87% | |||
AC Current (Typ.) |
0.8A/115VAC 0.6A/230VAC |
||||
Inrush Current (Typ.) |
COLD START 30A/115VAC 60A/230VAC |
||||
Protection: |
Over Load |
105 ~ 150% rated output power |
|||
Protection type : Hiccup mode, recovers automatically after fault condition is removed |
|||||
Over Voltage |
CH1:14.49 ~ 18.63V |
CH1:28.98 ~ 37.26V | |||
Protection type: Shut down o/p voltage, re-power on to recover |
|||||
Battery Cut Off |
10±0.5V |
20±1V | |||
Function: |
AC OK |
Open collector output, CONTACT : AC OK ; CUT OFF : AC Fail ; max. rating : 50V/30mA | |||
Battery Low |
Open collector output, CUT OFF : Battery ; CONTACT : Battery Low ; max. rating : 50V/30mA |
||||
Battery low voltage : < 11V |
Battery low voltage : < 22V | ||||
Environment: |
Working Temp. |
-30 ~ +70? (Refer to "Derating Curve") |
|||
Working Humidity |
20 ~ 90% RH non-condensing |
||||
Storage Temp., Humidity |
-40 ~ +85?, 10 ~ 95% RH |
||||
Temp. Coefficient |
±0.03%/? (0 ~ 55?) on CH1 output |
||||
Vibration |
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes |
||||
Safety & EMC |
Safety Standards |
UL60950-1, TUV EN60950-1 approved |
|||
Withstand Voltage |
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC |
||||
Isolation Resistance |
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25?/ 70% RH |
||||
EMC Emission |
Compliance to EN55022 (CISPR22) Class B, EN61000-3-2,-3 |
||||
EMC Immunity |
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61204-3, light industry level, criteria A |
||||
Others: |
MTBF |
536.6K hrs min. MIL-HDBK-217F (25?) |
|||
Dimension |
1.6 x 3.5 x 4 in (L*W*D) |
||||
Packing |
0.66 lbs; 42pcs/13.6Kg/0.82CUFT |
Electrical Specifications | |
Dimensions | 1.6 x 3.5 x 4 in (L*W*D) |
Number of Outputs | 1 |
Output Voltage | 27.6V |
PDF Specs | View Spec Sheet |
Wattage | 40 |
General | |
Industry Aliases | new |
DRC-40B
- Brand: Mean Well
- Product Code: DRC-40B
- Availability: Call for Availability
-
$66.10
- Ex Tax: $66.10